Sort the rooftop units by charge before you pitch the 15-pound rule
Since January 1, 2026, EPA leak-repair duties apply to many appliances holding 15 lb or more of HFC refrigerant. Check which units on a property manager's roof are covered and who carries each duty, then scope a maintenance agreement around what you find.

The 15-pound rule sells service agreements only when you can show a property manager which units on the roof it covers and who handles each duty. Since January 1, 2026, the leak-repair section of the federal regulation has applied to appliances with a full charge of 15 pounds or more of an HFC, or of a substitute with a GWP above 53. The same section excludes the residential and light commercial air conditioning and heat pump subsector. So your first sale is a paid asset register, built unit by unit, and you write the agreement around what the register finds.
Why the 15-pound pitch backfires when the unit isn't covered
On November 9, 2026 we asked four AI assistants how to use this rule to sell maintenance agreements, and they contradicted each other. One said the rule now reaches small rooftop units. Another, citing the regulation, said residential and light commercial air-conditioning and heat-pump equipment is excluded. Some answers did suggest mapping nameplates, recording the equipment category or checking unit by unit. None turned that into one rule for the rep: confirm both the charge and the subsector on each unit before you call it covered.
The regulation sides with the exclusion. Paragraph (a)(3)(ii) of 40 CFR 84.106 excludes the light commercial AC and heat pump subsector, whatever the charge. Tell a facilities manager an RTU is regulated, let the next contractor show them that paragraph, and you lose both the agreement and your credibility.
The old number still matters. A June 10, 2026 trade article reports that the AIM Act rule dropped the leak-repair threshold from 50 pounds to 15. A July 3, 2026 compliance guide notes that the 50-pound line still governs ozone-depleting refrigerants under Part 82, so an R-22 unit on the same roof stays under the older rules.
Build the asset register: nameplate charge, refrigerant, equipment class, exclusions
Under the 2026 HFC rule the owner must determine the full charge of every appliance holding 15 or more pounds of covered refrigerant, according to a March 5, 2026 compliance explainer. Your register does that work and covers the rest of the roof as well. Give every row these fields:
- Unit location, make and serial, so the record follows the equipment.
- Refrigerant from the nameplate, and whether it is an HFC, a substitute with a GWP above 53, or an ozone-depleting refrigerant.
- Full charge per circuit, from the nameplate or the manufacturer's data.
- Equipment class: comfort cooling, commercial refrigeration or industrial process refrigeration.
- Subsector check: does the unit fall in the light commercial exclusion, or is it a chiller or VRF system?
- Status: covered, not covered, or needs confirmation.
- Refrigerant added or recovered since January 1, 2026, if the owner has those records.
Two details change the count. An October 7, 2026 compliance guide points out that EPA treats each independent refrigerant circuit as a separate appliance (§84.102), with its own full charge. The same guide, citing EPA's fact sheet, says chillers and certain VRF systems sit in their own subsectors and fall outside the light commercial exclusion.
If a nameplate is unreadable, mark the unit as needs confirmation. A missing number tells you nothing about coverage either way, and the coverage call is yours to make on evidence.
What the owner must do once a unit is covered
The repair trigger depends on the equipment class. EPA's leak repair fact sheet, published in January 2026, sets the triggers below. Most of the rooftop and split equipment you service will sit in the comfort-cooling row.
LEAK-RATE TRIGGERS / 01.2026
Annual leak rate that triggers repair on a covered appliance
| Equipment class | Repair trigger |
|---|---|
| Comfort cooling | Over 10% |
| Commercial refrigeration | Over 20% |
| Industrial process refrigeration | Over 30% |
When a covered unit goes over its trigger, a fixed sequence of duties follows, as the October 7, 2026 guide and the regulation text lay it out.
OWNER DUTIES / 11.2026
What a covered unit's owner must do after a top-off
- Calculate the leak rate every time refrigerant is added, unless the addition immediately follows a retrofit or a new installation, or qualifies as a seasonal variance.
- If the rate exceeds the trigger, a certified technician finds and repairs the leak within 30 days of that refrigerant addition, or 120 days if an industrial process shutdown is required.
- Run an initial verification test inside that window. The follow-up comes within 10 days of a successful initial test, or within 10 days of return to normal operating conditions if the unit was evacuated.
- Inspect comfort-cooling appliances once a year after the follow-up test, until a year below the leak rate.
- Keep the records for at least three years.
Some states go further. The June 10, 2026 trade article reports that California, Washington and New York require repairs within 14 days on systems with 50 or more pounds of high-GWP refrigerant. It also reports an 8% comfort-cooling trigger in Washington and five years of records in New York and California. Check your state's rules before you write the agreement.
Write the agreement so each duty has a named owner
One assistant claimed an agreement shifts the legal headache off the building owner's plate. It doesn't. The regulation puts these duties on the owner or operator, and three of the four answers said so. Your firm's direct duty under paragraph (b) is to give the owner documentation every time you add or remove refrigerant.
Contractors still carry some risk. A November 8, 2026 insurance guide warns that indemnity clauses in service agreements can shift compliance costs onto the contractor, so write each duty down with a name next to it.
| Duty | Legal owner | What the agreement can say |
|---|---|---|
| Determine full charge | Owner or operator | Contractor builds the register; owner approves it |
| Document refrigerant added or removed | Person doing the service | Contractor delivers a record after every visit |
| Leak-rate calculation | Owner or operator | Contractor calculates and sends the result; owner keeps the file |
| Repair within the deadline | Owner or operator | Contractor quotes and schedules; owner authorizes |
| Initial and follow-up verification | Owner or operator | Contractor performs and records; owner keeps the file |
| Three years of records | Owner or operator | Contractor supplies copies; owner keeps the file |
Write "supports your compliance" in the agreement, never "guarantees compliance." Then spell out what happens if the owner declines a repair, delays access or has someone else add refrigerant.
Charge for the register visit as the first step into the agreement
Three of the four assistant answers floated a free or low-cost audit. Charge for it. The rule requires the owner to determine and record the full charge of each covered appliance, and a site-wide register goes past that requirement. Price it as fixed scope per site so the property manager can see it's real work. Whether you credit the fee against a signed agreement is up to you.
Then scope the agreement from the register. Covered units get a leak-rate log, a defined response window and verification visits; uncovered units get your standard planned maintenance. The regulation also lets the owner retrofit or retire a unit instead of repairing it, and if repairs fail to bring the rate down, the rule requires a retrofit or retirement plan. Either way, a replacement conversation may follow, on the owner's terms.
What to say when the manager asks, "Are we going to get fined?"
One assistant told contractors to warn of fines of tens of thousands of dollars per day and gave no source. Don't repeat it. You can't know what penalty a particular owner faces, and a number you can't back up will cost you the room.
Answer with the register. Show which units the rule covers, what happens the next time you add refrigerant to one, and who does each step. That gives the manager a list of named duties to decide on, and your agreement covers the ones they choose to hand you.
Maverick's part comes before the roof walk: finding the commercial buildings and the facilities manager who signs, so you have the register conversation with the person who decides. Reading the nameplate, making the coverage call, setting the scope and naming the price are your job.
Common questions
How do I tell if a 10-ton rooftop unit is even over 15 pounds?
Read the factory charge on the nameplate circuit by circuit, since EPA treats each independent circuit as a separate appliance. Tonnage won't tell you, so don't guess from it. Then check the equipment class, because the light commercial AC and heat pump subsector is excluded at any charge.
If the unit's covered, am I on the hook or is the owner?
Under 40 CFR 84.106 the owner or operator carries the leak-rate, repair, verification and recordkeeping duties. Your direct duty is to give the owner documentation whenever you add or remove refrigerant. Read your agreement's indemnity clauses too: a November 8, 2026 insurance guide warns they can shift compliance costs onto the contractor.
Can I charge for the asset register, or does it have to be free to get the agreement?
You can charge for it. The rule requires the owner to determine the full charge of each appliance holding 15 or more pounds of covered refrigerant, and a site-wide register goes past that. Price it as fixed scope per site and decide for yourself whether to credit it against a signed agreement.
What do I put in the contract so I'm not promising they'll never get fined?
Assign each duty to a named party and say the agreement supports the owner's compliance. Don't say it guarantees compliance. Spell out what happens if the owner declines a repair, delays access or has someone else add refrigerant, and note that state rules may add duties beyond the federal ones.
Does this apply to the new A2L units we're installing?
It depends on the refrigerant's GWP and the unit's class. The rule covers HFCs and substitutes with a GWP above 53, measured against table 1 of § 84.64(b), so check the new refrigerant against that table before assuming anything. The light commercial exclusion and the 15-pound full-charge threshold still apply on top of that.
Sources and dates
- 40 CFR 84.106 Leak repair, regulation text, read November 9, 2026
- EPA leak repair fact sheet, January 2026, read November 9, 2026
- EPA leak rate thresholds guide, July 3, 2026, read November 9, 2026
- Understanding EPA compliance thresholds, March 5, 2026, read November 9, 2026
- EPA refrigerant leak repair rules guide, October 7, 2026, read November 9, 2026
- Leak rules tighten as threshold drops to 15 pounds, June 10, 2026, read November 9, 2026
- EPA refrigerant recordkeeping and contractor liability, November 8, 2026, read November 9, 2026
Not measured: This post can't tell you whether a particular unit is covered or what penalty a particular owner faces. That depends on the nameplate charge, the equipment class and the current regulation text, so check each one before quoting it to a customer.